Product Overview
The S350 is a current vector inverter dedicated to the water industry, designed for constant pressure water supply with a constant pressure accuracy of 0.01MPa. It can efficiently drive induction motors and synchronous motors. The panel features a MASTER indicator light and supports master/auxiliary linked control. The auto-restart on power recovery function is enabled by default.
Technical Parameters
| Control Mode | Open-loop vector control (SVC), closed-loop vector control (FVC), V/F control |
| Maximum Frequency | Vector control 0~300Hz; V/F control 0~3200Hz |
| Carrier Frequency | 0.5kHz~15kHz, automatically adjustable according to load characteristics |
| Starting Torque | 0.5Hz / 110% |
| Speed Regulation Range | 1:100 (SVC), 1:1000 (FVC) |
| Steady Speed Accuracy | ±0.5% (SVC), ±0.02% (FVC) |
| Constant Pressure Accuracy | 0.01MPa |
| Torque Control Accuracy | ±5% (FVC) |
| Jog Control | Jog frequency range 0.00Hz~50.00Hz |
| Automatic Voltage Regulation (AVR) | Automatically maintains a constant output voltage when the grid voltage changes |
| Panel Indicators | READY (power/alarm), RUN (run/stop), COM (communication), SENSOR (sensor), MASTER (master/auxiliary) |
Application Scope
Constant pressure water supply systems, variable frequency retrofit of water supply pumps, and support for one-duty-one-standby and multi-pump linked water supply units. For matching power and voltage specifications, please consult and confirm according to the motor nameplate; installation wiring and parameter settings should be performed by professionals.
Operating Environment
| Ambient Temperature | -10℃~+50℃ |
| Humidity | Less than 95%RH (non-condensing) |
| Vibration | Not more than 0.6G, keep away from equipment such as punch presses |
| Protection Requirements | Prevent intrusion of water drops, steam, dust, fine metal powder, oil, salt and corrosive gases; keep away from electromagnetic interference sources |
| Prohibited Environments | Do not use in hazardous environments with flammable, combustible or explosive gases, liquids or solids |
Common Fault Codes
| Code | Fault | Common Causes and Troubleshooting Direction |
|---|---|---|
| Err.01P | Undervoltage fault | Instantaneous power failure, input voltage outside the specified range, abnormal bus voltage; reset the fault and adjust the voltage to the normal range |
| Err.02P | Overvoltage during acceleration | Input voltage too high, acceleration time too short; adjust the voltage to the normal range and increase the acceleration time |
| Err.03P | Overcurrent during deceleration | Output circuit grounded or short-circuited, deceleration time too short, voltage too low; eliminate peripheral faults and increase the deceleration time |
| Err.04P | Overcurrent at constant speed | Output circuit grounded or short-circuited, sudden load applied during operation, undersized selection; eliminate peripheral faults and select a higher power rating |
| Err.05P | Overcurrent during acceleration | Acceleration time too short, inappropriate V/F curve, voltage too low; increase the acceleration time and adjust the torque boost or V/F curve |
| Err.06P | Overvoltage during deceleration | Input voltage too high, deceleration time too short; adjust the voltage to the normal range and increase the deceleration time |
| Err.07P | Motor overload | Undersized selection, excessive load or motor stall; reduce the load and check the motor and mechanical conditions |
| Err.08P | Inverter overload | Undersized selection, excessive load or motor stall; select an inverter with a higher power rating |
| Err.09P | Inverter unit protection | Output circuit short-circuited, module overheated, internal wiring loose; eliminate peripheral faults and check the air duct and fan |
| Err.10P | Control power supply fault | Input voltage outside the specified range; adjust the voltage to within the specified range |
| Err.12P | Output phase loss | Abnormal leads from the inverter to the motor, three-phase output unbalanced; eliminate peripheral faults and check the three-phase motor windings |
| Err.20P | Input phase loss | Abnormal three-phase input power supply, abnormal surge protection board or main control board; check and eliminate peripheral circuit problems |
When fault handling involves wiring and internal components, please contact professionals.